Delta PROFIBUS-DP Module for VFD Series Drives PD-01 Manuel d'utilisateur Page 31

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 36
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 30
PD-01 PROFIBUS-DP Module
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
28
Edit the user parameters in S7 Step hardware configuration tools shown below:
NOTE:
Please do not set d_state to 1 when the address in Data Output 1 ~ Data Output 4 is
non-continuous to avoid Parameterization error and IO disconnect. The PD-01 just check the
address starting from Data Output 1 to Data Output [dout_len-1], in other words, if the
address in Data Output 1 ~ Data Output 3 is continuous, but the address in Data Output 4 is
not, and dout_len is 0x0003, then the check still can pass.
Vue de la page 30
1 2 ... 26 27 28 29 30 31 32 33 34 35 36

Commentaires sur ces manuels

Pas de commentaire