Chapter 2 Installation and Wiring| BLD-E1 Series
2-10 Revision May 2009, 00DE, V0.50
2.4 Control Terminals
Terminal symbols and functions
Terminal
Symbol
Terminal Function
Factory Settings (NPN mode)
ON: Connect to DCM
MI1 Forward-Stop command
ON: forward running
OFF: Ramp to stop
MI2 Reverse-Stop command
ON: reverse running
OFF: Ramp to stop
MI3 Multi-function Input 3
MI4 Multi-function Input 4
MI5 Multi-function Input 5
MI6 Multi-function Input 6
Refer to Pr.04-05 to Pr.04-08 for programming the
Multi-function Inputs.
ON: the activation current is 16mA.
OFF: leakage current tolerance is 10μA.
Specification Torque Wire
Terminal A, B 2 kgf-cm (2 in-lbf) 16-24 AWG (1.3-0.2mm
2
)