2. Programming Concepts
M1002
MOV K17 D1121
H86 D1120
K16
K16
M1351
END
SET M1120
MOV
MOV
D1434
D1450
MOV
M1350
X1
K16
K16
MOV
MOV
D1435
D1451
Retain communication protocol
Data length to be read from Slave ID
Data length to be written into Slave
Data length to be read from Slave ID
Data length to be written into Slave
Auto mode
Master ID#
COM2 communication protocol
#1
ID#1
#2
ID#2
b) automatically
into D1480 ~
and D1528 ~
When X1 = On, the data exchange between Master and the two Slaves will be
executed by PLC LINK. The data in D100 ~ D115 in the two Slaves will be read
D1495 and D1512 ~ D1527 of the Master, and the data in D1496 ~ D1511
D1543 will be written into D200 ~ D215 of the two Slaves.
Master PLC *1 Slave PLC*2
D1480 ~ D1495 D100 ~ D115 of Slave ID#1
D1496 ~ D1511 D200 ~ D215 of Slave ID#1
D1512 ~ D1527 D100 ~ D115 of Slave ID#2
D1528 ~ D1543 D200 ~ D215 of Slave ID#2
bling PLC LINK (M1350 = OFF) is
c) Assume the data in registers for data exchange before ena
as below:
Master PLC Preset value Slave PLC Preset value
D1480 ~ D1495 K0 D100 ~ D115 of Slave ID#1 K5,000
D1496 ~ D1511 K1,000 D200 ~ D215 of Slave ID#1 K0
D1512 ~ D1527 K0 D100 ~ D115 of Slave ID#2 K6,000
D1528 ~ D1543 K2,000 D200 ~ D215 of Slave ID#2 K0
After PLC LINK is enabled (M1350 = ON), the data in registers for data exchange becomes:
Write
Read
Read
Write
2-81